ADR-0133: Vitals methodology — widened-limit multiplicity, published MDE, and time-between-events charts

  • Status: Proposed
  • Date: 2026-08-09
  • Related: ADR-0120 (Stillness control architecture — the setpoint regulators + innovation-filtered sensing this methodology makes readable as evidence); ADR-0126 (Finder calibration — measures a finder's noise floor R; a per-instrument companion to this fleet-wide multiplicity ruling); ADR-0125 (Mutation gauntlet — gate sensitivity, another instrument that inherits these limits); ADR-0129 (Checkable-assertion density — one of the charts governed here). Governs the existing control-limit machinery in src/vitals/control.py (3.0·sigma_hat individuals chart), src/finder_calibration.py (DEFAULT_SIGMA_K = 3.0), src/audit/governance.py (upper_control_limit), and src/judge_independence.py (shewhart_c_chart_ucl).
  • Enforcement: enforced
  • Enforced by: pytest:tests/test_vitals_methodology.py
  • Binds: factory
  • Addresses: #10838 (Vitals methodology: pick a multiplicity regime, publish minimum detectable effect, fix rare-event charts). Everything downstream (#10367, #10370, #10373, #10829, #10836, #10837) inherits it.

This is a Proposed ADR — a design ruling for decision, not an accepted commitment. It formalizes the multiplicity regime the author already RULED in #10838 (widened limits, 2026-07-29), pins the arithmetic in an executable engine (src/vitals_methodology.py), and, deliberately, records what is settled maths today versus what is deferred migration (rewiring the live charts to consume it). The engine is a pure library, not a background loop, and it changes no live alarm threshold on its own. Accept, amend, or reject.

Context

The factory now runs a fleet of vitals instruments — finder calibration (#10821), judge calibration (#10836), the judge-independence c-chart, checkable-assertion density (#10917), the escape and erosion ledgers, the second-order vitals, the sampled re-audit's rate governor. Each is an individuals or c-chart with a limit at a hardcoded 3σ. Read one at a time, a 3σ chart is honest: an in-control process breaches it ~0.13% of the time (one-sided). Read as a fleet of ~70 charts, each evaluated on a cadence, the same 3σ produces a false alarm somewhere almost every cycle — and a fleet that always shows something adverse is a fleet nobody reads. This determines whether the vitals mean anything, and it must be settled before any of them are cited as evidence.

Three properties are missing, and #10838 researched each to a citable answer:

  1. A multiplicity regime. Classical SPC does not treat charts as hypothesis tests — it designs by average run length, and the Shewhart/Wheeler/Deming tradition rejects the p-value framing outright. There are three legitimate answers (widened limits; per-cycle Benjamini-Hochberg FDR; online FDR), and an ARL-designed chart with a BH-adjusted alarm gives neither guarantee. One must be chosen and never mixed.
  2. Power. A metric can be charted yet be incapable of detecting the effect it claims to monitor. A loop merging 30×/month at a 5% escape rate produces ~1.5 events/month; detecting a doubling on that volume takes ~7 months of pooling, so any monthly "escapes are flat" claim on it is not evidence.
  3. Rare-event handling. Count charts degenerate at low counts; the lower limit pins at 0 and a rate increase cannot breach it.

Decision

Four rulings, each with an executable anchor in src/vitals_methodology.py (tests in tests/test_vitals_methodology.py).

1. Multiplicity = widened limits, derived from the registered instrument count, decided at cycle granularity

RULED (author, #10838, 2026-07-29): widened limits. Benjamini-Hochberg FDR and online FDR are not adopted and must not be mixed in; we design by average run length and keep the Shewhart tradition the existing charts already assume.

  • The per-chart sigma multiplier L is a function of the registered instrument count (widened_sigma_multiplier(n_instruments)), splitting a family-wise monthly false-alarm budget (default 5%) across the fleet by Bonferroni (or Šidák). At 70 charts this is ~3.4σ rather than 3σ; the classic group-chart result (10 uncorrelated streams → 3.64σ, Mortell & Runger 1995; Epprecht 2011) is recovered by the same function with the matching arguments.
  • The widening factor is never hardcoded and never derives from a tick/evaluation count. It grows with the fleet, so the family-wise rate does not drift as instruments are added.
  • Floored at classic 3σ. We only ever widen: a small fleet under a loose monthly budget would compute a limit tighter than 3σ (a single chart at 5% is 1.96σ), which would over-alarm charts built for 3σ. The floor holds the fleet at classic Shewhart until it is large enough (n ≳ 19 at the 5% default) to genuinely need wider limits.
  • Alarms are decided at CYCLE granularity, not tick granularity (the #10838 blocker resolution). A chart's state is evaluated once per review cycle for alarm purposes; intermediate polls (trust_fleet_sanity_interval at 10 min, etc.) update data but cannot fire. Without this, the effective test count is charts × ticks — tens of thousands per month — and any fixed widening would leave the fleet reading permanently adverse. Cycle granularity gives an alarm the cleaner semantics of a statement about the cycle, and keeps the widening arithmetic dependent on chart count alone.

2. Alarm philosophy + triage budget (ISA-18.2 discipline — human cognition, not statistical false-alarm control)

Adopt the ANSI/ISA-18.2-2016 disciplines that are not statistical:

  • Rationalization. Every instrument's alarm must carry a documented operator response, a priority, and a consequence of inaction, or it is removed. AlarmDefinition.is_rationalized / rationalize() encode this; an un-actionable alarm is not a low-priority alarm, it is noise.
  • Triage budget. A review cycle carries a bounded triage budget (TRIAGE_BUDGET_PER_CYCLE, seeded at ISA-18.2's ~6 alarms/hour acceptable rate); RationalizationReport.over_triage_budget flags a fleet that exceeds it.
  • Cite ISA-18.2 for cognitive load only — never as false-positive control (that is pillar 1's job).

3. Publish a minimum detectable effect (MDE) per instrument, or stop charting it

mde_baseline_events(rate_ratio, alpha, power) returns the baseline events per window needed to detect a rate ratio, using the variance-stabilized Poisson approximation (z_{α/2} + z_power)² / (4·(√RR − 1)²) — which at α=0.05, 80% power reproduces #10838's published table (RR 2.0→11, 1.5→39, 1.25→141, 1.1→824, 0.5→23, 0.75→109, 0.9→745). can_chart(baseline_events, rate_ratio) refuses a rate chart whose MDE the instrument cannot meet. Seeded defects (#10835) are the way out of the power trap for gate-recall metrics: injected faults are as plentiful as chosen, so recall gets tight intervals where real escapes never will.

4. Move scarce-event metrics to time-between-events (g/t) charts

time_between_events_limits(mean_interval) gives the Benneyan (2001) g/t-chart limits — centreline 0.693·mean (the geometric median, since the distribution is badly right-skewed), UCL = mean + 3√(mean²+mean), LCL = max(0, mean − 3√(mean²+mean)). Because the LCL pins at 0, deterioration (intervals collapsing toward 0) cannot breach a limit; consecutive_zeros_run_limit() supplies the Benneyan consecutive-zeros run rule so it still shows. Metrics like merges-between-escapes and days-between-escapes move to these charts.

Consequences

  • The vitals become citable as evidence. A widened-limit breach at cycle granularity, on an instrument whose MDE it meets, means what it says; a flat reading on a metric below its MDE is explicitly not evidence and is labelled so.
  • This ADR changes no live threshold by itself. The four call sites that hardcode 3.0 (vitals/control.py, finder_calibration.py, audit/governance.py, judge_independence.py) continue to read 3σ until a follow-up migration rewires them through widened_sigma_multiplier against a real registered-instrument count. That migration is a deliberate behavior change to live alarms and gets its own PR + review; it is out of scope here so the methodology can be accepted independently of moving every chart at once.
  • Mixing regimes is now a documented violation. Introducing a BH-adjusted or online-FDR alarm alongside these ARL-designed charts contradicts this ADR and requires a superseding one.
  • Config cadences mismatched to their measurement window (#10843) reduce the effective test count directly and are a separate config change, not a statistics change.

Alternatives considered

  • Per-cycle Benjamini-Hochberg FDR (convert each chart to a p-value via Li, Qiu, Chatterjee & Wang 2013, then BH over "this month's review"). Defensible and auditable, but BH assumes independence or positive dependency and these series (escapes, erosion, interventions) are almost certainly correlated; Benjamini-Yekutieli handles arbitrary dependence at a log(m) cost. Rejected: mixing it with ARL-designed charts gives neither guarantee, and the author RULED against adopting it.
  • Online FDR across the stream (LOND/LORD; SAFFRON/ADDIS) for a lifetime rather than per-month guarantee. Rejected for the same non-mixing reason, plus alpha-wealth budgeting makes quiet metrics progressively stingier — the wrong failure mode for a factory whose quiet metrics are the ones we most want to keep sensitive.
  • Tiered BH in production (Optimizely's primary/secondary/monitoring split at ~10% FDR alongside always-valid p-values). Strong precedent, but it is the FDR regime this ADR declines; kept on record as the shape to copy if a future superseding ADR ever adopts FDR.
  • Leave every chart at a naive 3σ. Rejected: that is the status quo that makes the fleet unreadable as it grows — the exact problem #10838 exists to fix.